Basic properties

  • Dry powder mass: 96 kg
  • Protected volume: 420 m3
  • Protected area: 150 m2
  • Operation temperature: -50...+95°C
Ask a question

Ask a question about the
Installation of powder fire extinguishing “Buran-100ST-ESG”

Your name
Country
Company
Your site
Your contact phone
Your e-mail
Your question

TO ORDER

To order
Installation of powder fire extinguishing “Buran-100ST-ESG”

Your name
Country
Company
Your site
Your contact phone
Your e-mail
Quantity for order
Order description*

The Buran-100KD-ESG powder fire extinguishing installation is a set of two Buran-50KD powder fire extinguishing modules (U1) with ESG-0.5 electric igniters, placed on a special stand and intended for localization and extinguishing fires of class A, B, C, as well as fires arising in electrical equipment under voltage up to 1000 V.

The installation is used as an actuator in automatic fire extinguishing installations and belongs to the class of stationary fire extinguishers, does not contain ozone-depleting substances.

The unit is not designed to extinguish the fires of alkali and alkaline earth metals, as well as substances whose combustion can occur without air access.
Climatic modification — U1 according to GOST 15150-69 for ambient temperature from minus 50ºC to plus 95ºC at relative humidity up to 98%.

The primary field of application is the technical premises of large areas and volumes in industrial and residential buildings, warehouses for various purposes, transformer substations of closed and open types, open storage and production sites.

Specifications

  • Degree of protection from external influences: IР54
  • Module Mass:  180 kg
  • Dry Powder Mass: 96 kg
  • Length: 480 mm
  • Width: 700 mm
  • Height: 1030 mm
  • Protected area when extinguishing class A foci with a spraying height of 3 ÷ 5 m: 150 m²
  • Protected area when extinguishing class B foci with a spraying height of 3 ÷ 5 m: 120 m²
  • Protected volume when extinguishing class A foci: 420 m³
  • Protected volume when extinguishing class B foci: 360 m³
  • Actuation current: 0,5 A
  • Safe current monitoring of the electrical circuit is not more than 0,1 A
  • Electrical resistance: 3,2 … 5,0 Om
  • Operation Temperature: -50…+95 °C
  • Storage Temperature: -50…+50 °C
  • Service Life: 10 years
  • Module is considered to be the main element of fire extinguishing systems

REQUIREMENTS TO PIPELINES

  • Diameter of the conduit passage of the extinguishing powder feeding pipe: 25 mm.
  • The length of the pipeline in the horizontal direction is no more than 30 m.
  • The lifting of the pipeline from the base of the shell in the vertical direction is no more than 6 m.